ELECTRO-PNEUMATIC TRANSDUCERS@RT SERIES
¥With the use of incorporated Floating system , RT Series Transducers reduce a supply pressure to a regulated Output pressure which is directly proportional to an Electric Input Signal.
Available in Model RTEI/P

EHighly accurate control of air pressure.
Linearity ( 1.0 to 1.5 % ) F.S.
Hysteresis … }1.0% F.S

EOutstanding low supply pressure Sensitivity.
Output pressure is virtually unaffected (… }0.5 % F.S ) by variations in supply
pressure.

ELarge Flow Rate allows direct drive of pneumatic control devices.

EField Reversible.

EExcellent Repeatability
Normal load … 2.5 % F.S.
Intermittent load … 0.5 % F.S.

EWide Adjustment Range.
Span Adjust Range :
Model RTEE/P-8-2 0.65 to 0.82 MPa
Model RTEI /P-8-2 0.24 to 0.82 MPa

EMounts at Any Angle.
Zero/Span Readjustment required.

ESmall size permits use in restricted areas.

EPrincipal Dimensions  54~105
Specifications
Model RTEE^P|8|2 RTEI^P|8|2 RTEI^P|1|2
Working Fluid Clean Compressed Air
Set Pressure Range@MPa 0.02`0.82 0.02`0.1
Input signal Control System Voltage (2-line) Current (2-Wire)
Voltage VDC 0`10 |
Impedance ƒ¶ 805 |
current mADC | 4`20
Impedance ƒ¶ | 260 180
Linearity@“.F.S 1.5 1.0
Hysteresis@“.F.S 1.0
Repeatability@“.F.S }0.1 }0.5
Step Response@sec 1.0 0.2
Span Adjust Range@MPa 0.65 to 0.82 0.24 to 0.82 |
Relief Sensitivity@MPa Set Pressure Range{0.001ˆÈ‰º
Air Consumption@Nl/min 3.7 ˆÈ‰º 4.8 ˆÈ‰º
Range of Working Temperature@Ž 5 ` 60
Pipe Port@RciPTj 1^4
Gauge Port@RciPTj 1^4
mounting Bracket (Standard)
Weight@kg 0.94



Ordering Information

RT E E^P | 8 | 2 | G025
‡@ ‡A ‡B

‡@ ‡A ‡B
Input Signal Set Pressure Range option
(Pressure gauge)
E^P Voltage Conversion System 1 0`0.1MPa G025 0`0.025MPa
I^P Current Conversion System 8 0` 0.82MPa G060 0`0.6MPa
G010 0`1MPa




For further details, refer to, Cat.NoDKS|130E
For further details, refer to,CADdata

–ß‚é